In healthcare buildings the floor must withstand disinfection, avoid trapping dirt in joints and corners, and last despite trolley and bed traffic.
Hygiene comes first
Hospital and clinic floors are disinfected frequently. Joints and corners are places where microorganisms can settle, so seamless systems that continue into coved skirting are preferred. HBN 00-10 Part A, the English health building guidance on flooring, also recommends avoiding carpets in clinical areas.
A continuous floor-to-wall return
According to the same guidance, there should be a continuous return between floor and wall in clinical areas and their corridors; coved skirtings at least 100 mm high are given as an example. This detail lets cleaning reach right into the corner. Similar requirements in laboratories are covered in laboratory flooring.
Detergents and disinfectants
Long-term resistance to chlorine- and alcohol-based disinfectants is decisive. HBN 00-10 states that floor finishes should not be physically affected or degraded by the detergents and disinfectants likely to be used. Compatibility is checked in the system's technical data sheet, and the list of products in use is given to the contractor at the outset (how to read a chemical resistance chart).
Trolley and bed traffic
Wheeled stretchers, beds and equipment wear corridors constantly. The guidance asks for corridors to withstand heavy wheeled traffic and intensive pedestrian traffic, and for the floor to provide a flat surface without pronounced texturing so that wheeled traffic moves easily and maintenance is simpler. An abrasion-resistant, easily repairable system pays off in the long run.
Balancing grip and texture
The floor must prevent slipping both in areas considered dry and in those that get wet in use. The table in Germany's ASR A1.5 specifies R9 for wards, corridors and operating theatres, R10 for sanitary rooms and ward bathrooms, and R11 for wet disinfection rooms. Because of wheeled traffic, the texture should be no rougher than necessary (slip resistance ratings).
Monitoring slip resistance
HBN 00-10 expects healthcare providers to monitor a floor's slip resistance at regular intervals throughout its service life to identify changes. Films left by care products, wear and the wrong cleaning method can alter grip over time, and the measurements are also used to review the cleaning programme.
Thresholds and manhole covers
The guidance asks for threshold strips to be avoided and does not consider manhole covers or inspection chambers acceptable in clinical areas. Seamless poured resin floors suit threshold-free transitions between rooms and corridors; where different floor types meet, the junction is made flush and cleanable.
Operating theatres
Under HBN 00-10, operating theatre floors must withstand the rolling loads of heavy mobile equipment, frequent spillages, regular cleaning and disinfection. The finish must adhere firmly to a smooth, crack-free and stable subfloor. Where antistatic performance is required, the system is chosen accordingly (antistatic epoxy flooring).
Wet rooms and entrances
The guidance requires floors in sanitary spaces to stop moisture penetrating the building fabric, and floors regularly exposed to water to resist liquid penetration (is epoxy flooring waterproof). In wet zones, such as behind pre-plumbed panels, the risk of flooding and bacterial growth is addressed in the detailing. At entrances the floor must be slip-resistant in all weather, with no unprotected strip between threshold and matting, and the matting must suit trolleys and wheelchairs as well as pedestrians and be cleaned regularly.
Quiet and comfort
Footstep noise can be disturbing in wards and corridors. Flexible polyurethane-based systems are quieter and more comfortable underfoot than hard surfaces (polyurethane floor coating). HBN 00-10 asks for acoustics to be considered in the risk assessment carried out before a floor is specified.
Choose by department
Operating theatres, laboratories, corridors and waiting areas have different needs; the flooring system is assessed separately for each, and, as the guidance requires, the assessment is recorded. Renovation in a working hospital is planned area by area (phased installation).
Frequently Asked Questions
Why are seamless floors preferred in hospitals?
Joints and corners can trap dirt and microorganisms; a seamless surface makes cleaning easier.
Do hospital floors withstand disinfectants?
A suitable system withstands regular disinfection; compatibility is checked in the data sheet.
How can corridor noise be reduced?
Flexible polyurethane-based systems are quieter than hard surfaces.
How high should skirting be in a hospital?
The English HBN 00-10 guidance calls for a continuous floor-to-wall return in clinical areas and corridors and gives coved skirting at least 100 mm high as an example.
Would you like a site survey for your floor? HBK Epoxy Flooring, based in Gaziantep, offers free surveys and quotations in the surrounding provinces.
0507 597 9537 WhatsAppRelated articles

Parking Space Dimensions: Bay Sizes Under Turkey's Car Park Regulation
Turkey's Car Park Regulation sets a minimum of 2.40×4.90 metres for a car parking space and a minimum width of 3.50 metres for an accessible bay. Line layouts are planned with these sizes and the aisle.
Read article ›
Car Park Floor Coatings: Protection Against Salty Water and Slush in Winter
In winter, cars bring snow, slush and road de-icing salt into car parks. This salty water can penetrate concrete and reach the rebar; the right coating, falls and maintenance protect the deck.
Read article ›
Is Epoxy Flooring Suitable for Homes? Living Room, Kitchen and Bathroom
Epoxy can be used at home too, but a house brings different expectations from a factory. The substrate, grip in wet rooms and sunny windows decide the right choice.
Read article ›